The above variable air volume (VAV)
supply air system fan requires 20,500 cfm @ 3 in.w.g. SP, which includes
400 cfm or 2 percent estimated duct air leakage.
The VAV boxes need a minimum
of 1 in.w.g. at the box inlet, rectangular and flat oval duct aspect
ratios cannot exceed 3:75 to 1.
Ductwork shall be sealed as per ASHRAE/SMACNA
seal classes B for 3 in.w.g. and C for 2 in.w.g. construction pressure
classifications.
All elbows will have RiD = L5, transitions = 30° slope, branch
taps = 45° angle with 45° elbows, and wye fitting = 45° angles
with 45° elbows.
All duct branches to VAV boxes have balancing dampers.
All ductwork will
he galvanized steel with gauges and reinforcement as per the SMACNA 111/AC
Duct Construction Standards 1985.